GU ELECTRIC — Beyond the CabinetGU ELECTRIC — Beyond the Cabinet Get a quote
Home/Products/Control & Automation Cabinets/Air handling unit control cabinets
B U I L D T O D R A W I N G PLC stainless steel control cabinet · Photo 01
PRODUCT — 01 · Control & Automation Cabinets

Air handling unit control cabinets

Temperature and humidity are process parameters, not just comfort
Model GU-HVAC · Temperature/humidity acquisition · Fan VFD · Valve linkage · MOQ 1 unit
The AHU control cabinet handles start/stop interlock, fan speed control, temperature and humidity acquisition, and water valve / fresh air damper linkage for air handling units (AHUs): on startup, open the valve before starting the fan; on shutdown, reverse the sequence. In low winter temperatures, freeze protection forces the hot water valve open, stops the fan, and alarms. The control core is a PLC or dedicated controller selected by point count, with fan speed controlled by a VFD. Supply/return air temperature and humidity, filter differential pressure, and freeze protection switches are all wired back to the cabinet for data acquisition. Temperature control accuracy is ±1 °C as standard.
  • Interlock: open valve → soft-start fan → supply air; reverse on shutdown. If the sequence is wrong, the cabinet will not execute.
  • Temperature control: supply/return air temperature and humidity acquisition; PLC or dedicated controller closed-loop adjusts water valve position
  • Freeze protection: when the low-temperature freeze switch trips, the hot water valve is forced fully open, the fan stops, and an alarm is raised
  • Fan: VFD speed control automatically adjusts airflow based on temperature deviation; filter differential pressure alarm for maintenance reminders
  • Components: Schneider / ABB / Siemens / Chint; brand can be specified, or customer-supplied components shipped to our plant
±1 ℃Temperature control accuracy (standard process)
4–20 mATemperature/humidity transmitter inputs
≤7 zonesTypical temperature control zones
1 unitMOQ 1 unit · ≥5 recommended for volume production
01 — SPECIFICATION

Specifications

The table below covers 80% of factory distribution room cases. Anything outside it we can still build — those are engineered items, quoted separately, with an indicative price the same day.

TypeFloor-standing as standard, installed in mechanical rooms; wall-mounted for small fresh air units
Standard sizes (W×D×H)800×600×1800 / 1000×800×2000 mm, custom build available
Enclosure construction2.0 mm cold-rolled carbon steel; separate compartments for control and VFD sections; heat dissipation duct
IP ratingIP54 standard / IP65 optional (dusty mechanical room environments)
Operator panelTemperature/humidity display, start/stop and mode selection, fault and filter alarm indicators
Environmental adaptationAnti-condensation heater inside the cabinet when mechanical room temperature drops below 0 °C in winter
Rated operating voltageAC 380V / 400V main circuit; AC 220V / DC 24V control
Control corePLC (many I/O points / communication required) or dedicated temperature controller (few points)
Fan controlVariable frequency speed control (based on temperature deviation) or two-speed / direct-on-line, configured per unit model
Temperature and humidity acquisitionSupply / return air temperature and humidity transmitters, 4–20 mA; dew point and CO₂ optional
Valve interlockingWater valve modulation (0–10V / 4–20mA), fresh air damper and exhaust damper on/off signals
Freeze protectionFreeze protection switch (low-temperature cutoff) forces the hot water valve fully open, stops the supply fan and raises an alarm
Interlock sequenceStartup: open valve → time delay → fan; shutdown: stop fan → time delay → close valve
Communication interfaceModbus RTU / TCP reserved for connection to building BA or a host system
Component brandsSchneider / ABB / Siemens / Chint; customer-supplied components accepted for factory installation
Two-pipe constant temperature typeSupply air temperature closed-loop control of the water valve; coil shared between heating and cooling; suitable for plants and offices
Four-pipe constant temperature and humidity typeSeparate chilled and hot water valves control temperature; humidifier and reheat control humidity; accuracy ±1 ℃ / ±5% RH
Fresh air handling unit typeSupply air temperature control with freeze protection as the primary function; exhaust air interlock optional
Cleanroom air handling typeConstant air volume with variable frequency pressure stabilization (supply duct static pressure closed loop); differential pressure alarm for the high-efficiency filter section
Multi-unit group controlOne cabinet controls multiple units, with rotation of unit count and centralized interlock management; connects to BA
Assembly standardGB/T 7251.1 / IEC 61439-1
Interlock verificationVerify start/stop interlock sequence and freeze protection override logic unit by unit
Routine tests (every unit)Insulation resistance, power frequency withstand voltage, and closed-loop commissioning by energizing simulated temperature signals
Temperature riseIndependent air duct for the VFD section; temperature rise inside the cabinet ≤15 K
Documents with shipmentSchematic diagram, I/O point list, interlock sequence description, BOM, test report
02 — CONFIGURATOR

Five steps to specify your run

A configuration summary is generated as you go. It travels with your inquiry, saving a round of confirmation.

01Unit type
02Fan mode
03Control core
04Temperature control accuracy
05Options (multiple)
03 — CRAFT

Build details

Systems have been in service for decades, and the failure points are always the same few: poor busbar contact, water ingress at the door seal, high temperature rise in the correction cabinet, and mis-phased outgoing feeders. The six hard rules below are written for exactly these points — every cabinet can be traced to them.

Fixed timing sequence

On startup, open the valve before starting the fan

Start/stop interlocks are hard-coded in the cabinet: if the sequence is wrong, it will not run — no coil freeze-up, no damper overpressure. This logic does not depend on the operator remembering it.

Forced freeze protection

At low temperature, valve opens and fan stops

The freeze protection switch is wired into a hardwired safety circuit, so it still trips if PLC communication is lost: hot water valve forced fully open, fan stopped, audible and visual alarm. Better to run hot than to freeze and split the coil.

Simulated loop check

Temperature signals injected unit by unit

At the factory, a signal generator simulates temperature and humidity for closed-loop commissioning; the full control curve and alarm logic are exercised. On site, only sensor calibration is needed.

Separate Compartments for Heat Dissipation

Isolated air duct for the VFD

The VFD sits in its own compartment with a dedicated air duct, so its heat does not bake the controller; even on hot days in the equipment room, the temperature rise inside the cabinet stays within 15 K.

Separated wiring routes

Individual shielding for analog signals

Temperature and humidity 4–20 mA signals use individually shielded twisted pairs with single-point grounding, routed in separate trays from power cables, so readings do not jump.

Point list delivery

Every point traceable

I/O point list ships with the panel: terminal, range, and alarm value for every sensor and actuator point are documented, so the BAS reads to the table.

04 — EVIDENCE

Photos & enclosure construction

Below are photos taken in our own shop — from the complete unit down to the internal busbars and secondary wiring. Every build detail can be checked item by item.

PLC stainless steel control cabinet · Photo 01
PLC stainless steel control cabinet · Photo 01
PLC stainless steel control cabinet · site photo 02
PLC stainless steel control cabinet · site photo 02
PLC stainless steel electrical control cabinet · Photo 03
PLC stainless steel electrical control cabinet · Photo 03
FRONT VIEW Power meter Status indication Channel base at the bottom · inter-cabinet busbars run through H 2200 W 800 / 1000 / 1200 IP54 standard IP65 optional Ue 400V ≤2000A Icw 30–65kA
Verifiable build checklist:2.0 mm seam-welded enclosure · diagonal ≤1.5 mm · busbar torqued to 30-40 N·m with witness marks · busbar joint temperature rise ≤70 K · segregated wiring compartments · CTs and meters in separate compartments · 60-80 μm coating · 2500 V/1 min withstand on every unit.

Image key: 01–05 are shop photos (the numbers match the shot list). The line drawing shows the front elevation of the enclosure; dimensions match the specification table above.

05 — APPLICATIONS

Where these cabinets go

These are the routine applications — we can talk scheme and configuration directly. For the industry view, see the industry pages.

Process air conditioning for plants

The primary solution when workshop temperature and humidity affect the process (coating, electronics, printing).

Cleanrooms and laboratories

Constant air volume with stable pressure operation, high-efficiency filter differential pressure monitoring, and layered temperature/humidity control.

Constant temperature and humidity equipment rooms

±0.5 °C / ±3–5% RH control for precision equipment and metrology rooms.

Commercial air handling units

AHU group control for shopping malls and office buildings, interfaced with the building BAS.

Fresh air and exhaust air interlock

Fresh air damper modulates on CO₂ concentration, balancing energy savings with air quality.

Winter freeze protection

Standard protection for northern equipment rooms and fresh air handling units operating in winter.

06 — TERMS

Commercial terms

Specification dated September 2026; quotations follow this.

Drawings & designFree
MOQ1 unit (5 or more recommended for production)
Production lead time15-25 days after drawing approval
on-time delivery98%
Warranty12 months
Loading portNingbo / Shanghai, China
Component brandsSchneider / ABB / Siemens / Chint
Factory visit & dispatch confirmationFactory visits welcome; finished-cabinet photos and video before dispatch
Capacity5,800+ units / year
07 — DOWNLOADS

Documents for your engineering team

Selection manual, outline dimensions and RFQ checklist — for the customer's electrical engineer. All three documents are being organized by product line; download links go live once complete.

PDFSelection and configuration manualTechnical highlights, specifications, typical solutions and commercial termsIn progress · pending
DXFCommon outline & cut-out dimensionsFront view / side view / foundation and cable entry cutoutsIn progress · pending
XLSRFQ data checklistInformation to confirm before quoting — fill in and send backIn progress · pending
08 — FAQ

Six questions procurement and electrical engineers ask most

Why does AHU start/stop need an interlock sequence?

On startup, open the water valve before starting the fan: blowing air through a coil that has no hot water yet will freeze and split the coil in low-temperature periods. Shutdown runs in reverse order so residual coil heat dissipates before the valve closes. These sequences are hard-coded in the cabinet — the operator presses one button.

What does constant temperature and humidity require?

Temperature: split-range control of the chilled/hot water valve. Humidity: steam or electrode humidifier, with dehumidification by cooling the coil to condense moisture, plus reheat if needed. ±1 °C / ±5% RH is achievable as standard; ±0.5 °C depends on the room envelope and steam source, so we work that out together at the proposal stage.

How exactly does freeze protection act?

A freeze protection switch (capillary or low-temperature cutout) is mounted on the leaving-air side of the coil. Below the setpoint (typically 5 °C) it opens: a hard-wired circuit forces the hot water valve fully open, stops the supply fan, and triggers audible and visual alarms. It does not go through the PLC — it still acts if the controller fails.

Can it interface with the building BAS?

Modbus RTU / TCP interface is reserved, with the point list mapped to the BAS contractor's requirements; BACnet is handled by adding a gateway. Typical split of scope: we handle unit-level control, the BAS handles global scheduling and monitoring.

VFD or two-speed for the fan?

Choose a VFD for temperature-adaptive airflow and soft starting (better on both energy and comfort); choose two-speed if the budget is tight and only two stages are needed. VFD is already mainstream on large units — we build both panel types.

Can one cabinet control multiple units?

Yes. A group control cabinet centralizes unit staging and rotation, with the unit's own valves and fan on separate output circuits. Above 4 units, or when equipment rooms are spread out, we recommend separate cabinets plus supervisory scheduling; the topology is drawn out in the proposal.

09 — RELATED

Other cabinet types in the same main circuit

Related products use color-block placeholders for now (product photos not yet complete; they will be replaced together). Internal links will be filled in once live URLs are confirmed.

09+ — SOLUTIONS

How this product is applied in the industry

Operating details, cabinet combinations and customization points are covered in the industry application page — go there directly.

10 — RFQ

Send us the unit drawings and we will hard-code the interlocks to them

Send us the AHU drawings or point list and we will provide a free control solution and interlock sequence diagram · Quotation within 24 hours. Direct from the source factory, MOQ 1 unit, 15–25 day delivery, 1-year warranty.

Email your inquiry WhatsApp: +86 186 5712 0011
GU ELECTRIC (Zhejiang Golden Unicorn) · 5,000 sqm workshop, Fengchuan Industrial Zone, Tonglu · 20 people · 5,800+ units per year
ISO 9001:2015 · CE(LVD+EMC) · CQC · IP65

When you write, include: single-line diagram or primary scheme, switch room layout, load list, and component brand requirements. You do not need complete drawings — capacity and cabinet type are enough to start.

Air handling unit control cabinet · MOQ 1 unit · 15–25 days Get a quote