HomeTechnical notes › How to Read the Explosion-Proof Rating on an Explosion-Proof Distribution Box: Gas Group IIA/IIB/IIC + Temperature Class T1–T6, a Complete Guide to Explosion-Proof Markings

05 Informational content / Technical articles 2026-09-11 Published ~ 11 min read GB 3836.1

How to Read the Explosion-Proof Rating on an Explosion-Proof Distribution Box: Gas Group IIA/IIB/IIC + Temperature Class T1–T6
A Complete Guide to Explosion-Proof Markings

The explosion-proof rating is the "identity code" of an explosion-proof distribution box: the gas group (IIA/IIB/IIC) determines how severe a flame propagation it can contain, and the temperature class (T1–T6) determines the maximum surface temperature allowed. This article follows GB 3836.1(Explosive Atmospheres — Part 1: General Requirements) to break down each segment of the explosion-proof marking, with a group-temperature reference table for common hazardous gases. Zhejiang Golden Unicornoffers joint supply with an Ex-qualified manufacturer, holds ISO 9001:2015,MOQ 1 unit · 15–25 days.

1. The Complete Structure of an Explosion-Proof Marking (It Is Not Just d and T4)

A complete explosion-proof marking for a gas atmosphere:Ex d ⅡB T4 Gb— Ex (explosion protection) + d (flameproof enclosure) + IIB (gas group) + T4 (temperature class) + Gb (Equipment Protection Level, EPL). For dust atmospheres, the marking takes the form Ex t IIIC T80°C Db. When selectingevery segment must match the site conditions, and if any segment falls below the requirement, the unit cannot be used.

SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — 1. The Complete Structure of an Explosion-Proof MarkingCabinet structure diagram · photo pending

2. Gas Group: IIA/IIB/IIC (Dual Criteria: MESG + MIC)

Gas groups are classified by flame propagation capability, using two criteria:Maximum Experimental Safe Gap (MESG)andMinimum Ignition Current ratio (MIC)Dual criteria:

GroupMESGTypical gasesTypical applications
IIA≥ 0.9mmPropane, methane, ammonia, acetoneRefining, wastewater treatment
IIB0.5–0.9mmEthylene, propylene, city gasPetrochemical cracking, coal gas
IIC≤ 0.5mmHydrogen, acetylene, carbon disulfideHydrogen production, electrolysis, acetylene plants

Downward compatible: IIC equipment can be used in IIB/IIA gas atmospheres, but not the reverse. Acetylene atmospheres require IIC.

3. Temperature Class: T1–T6 (Maximum Surface Temperature)

GroupMaximum surface temperatureTypical gas (ignition temperature)
T1≤ 450°CMethane (537°C), hydrogen (560°C)
T2≤ 300°CEthylene, acetylene (305°C)
T3≤ 200°CGasoline, hydrogen sulfide
T4≤ 135°CAcetaldehyde, diethyl ether
T5≤ 100°CCarbon disulfide (≈100°C)
T6≤ 85°CEthyl nitrate

4. EPL — Equipment Protection Level (Ga/Gb/Gc correspond to zones)

Cross-reference

Ga(very high protection, e.g. ia/ma) → Zone 0;Gb(high protection, e.g. d/e/p/mb) → Zone 1;Gc(normal protection, e.g. n) → Zone 2. For dust atmospheres the equivalent is Da/Db/Dc → Zone 20/21/22. When selecting, the zone sets the level, the gas sets the group, and the ignition temperature sets the T class.

SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — 4. EPL — Equipment Protection LevelCabinet structure diagram · photo pending

5. Common scenarios — quick reference (match your site)

ApplicationAtmosphere gasRecommended marking
Gas station (submerged pump area)Gasoline vapor (T3)Ex d ⅡA T3 Gb
Hydrogen generation plantHydrogen (T1, IIC)Ex d ⅡC T1 Gb
City gas pressure regulating stationNatural gas (T1, IIA)Ex d ⅡA T1 Gb
Acetylene cutting shopAcetylene (T2, IIC)Ex d ⅡC T2 Gb
Baijiu distilleryEthanol (T2, IIA)Ex d ⅡA T2 Gb

FAQ FAQ

How do I find the gas group and ignition temperature for my site?

Check the GB 3836.1 annexes and standard flammable gas property tables, or have the design institute / owner specify it on the hazardous area classification drawing.

Is there a problem if I select a higher rating than needed?

No safety issue — it is justmore expensive and heavier(IIC enclosures cost considerably more). Select for the actual gas; when in doubt, go higher rather than lower.

Can T4 equipment be used in a gasoline atmosphere?

Yes. Gasoline is a T3 atmosphere (ignition temperature on the order of 280°C). T4 equipment has a lower maximum surface temperature (stricter), so it is downward-compatible with T3; the reverse does not hold — T3 equipment cannot be used in a T4 gas atmosphere.

How is the rating marked for dust atmospheres?

Use Ex t + IIIA/IIIB/IIIC + the specific temperature (e.g. T80°C Db); the T1–T6 gas groups do not apply.

Related pages:Technical notes · Products · Industries · Resource center · FAQ · Get a quote

Related reading

Need Distribution box, distribution cabinet? Build to drawing · MOQ 1 unit · 15–25 day delivery

A source factory in Zhejiang (Fengchuan Industrial Zone, Tonglu — 5,000 sqm, a team of 20, 5,800+ units a year), holding ISO 9001:2015 / CE(LVD+EMC) / IP65 test report. Build-to-drawing service for distribution boxes, low-voltage assemblies, PLC control cabinets and VFD panels. Free drawing review, photo/video inspection before shipment.