HomeTechnical notes › How to Read a Fan Control Cabinet Wiring Diagram: Star-Delta / VFD / Two-Speed Fan

05 Informational content / Technical articles 2026-09-11 Published ~ 11 min read GB/T 6988.1

How to Read a Fan Control Cabinet Wiring Diagram
Star-Delta / VFD / Two-Speed Fan

Fan control cabinets come in three typical configurations — star-delta starting, VFD speed control, and two-speed motor switching, each with a different wiring diagram. This article follows GB/T 6988.1 to break down all three fan control cabinet wiring diagrams. Zhejiang Golden Unicorn fan control cabinets cover the full 7.5kW to 250kW power range, ISO 9001:2015 certified,MOQ 1 unit · 15-25 days · 98% on-time.

1. Fan Load Characteristics and Starting Method Selection (Comparison of 3 Configurations)

Fans arevariable-torque loads(power ∝ speed³), with low starting torque but high inertia. Three starting methods:

ConfigurationApplicable PowerStarting CurrentAdvantagesDrawbacks
Direct-on-line starting≤7.5kW4-7x IeSimple, low costHigh inrush
Star-delta starting7.5~55kW1/3 of direct-on-line starting currentModerate costSwitching inrush
VFD speed control11~250kW+Adjustable from 0 to rated30-50% energy savingsHighest cost
SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — 1. Fan Load Characteristics and Starting Method SelectionCabinet structure diagram · photo pending

2. Star-Delta Fan Control Cabinet Wiring Diagram (Main Circuit + Time Relay Switching)

The star-delta starting wiring diagram for fans is similar to that for pumps, but thetime relay setting is longer(High fan inertia, long acceleration time):

  1. Main circuit: QF breaker → KM1 main contactor → KM2 star contactor (start) → KM3 delta contactor (run) → thermal overload relay FR → motor (delta connection, 6 terminals U1/V1/W1/U2/V2/W2).
  2. Control circuit: Start button SB2 → KM1 self-hold + KM2 energized + KT energized. After the KT delay (typically 15–30 s), KM2 opens → KM3 energizes → motor switches from Y to delta run.
  3. Interlock: KM2 and KM3 normally closed auxiliary contacts interlock to prevent simultaneous pull-in and short circuit.
  4. Damper interlock: Large fans require the damper closed before start (to reduce starting load); KM1 auxiliary contact interlocks the damper actuator.

3. VFD Fan Control Panel Wiring Diagram (VFD + PID + temperature control)

Compared with pump panels, the VFD fan control panel addsClosed-loop temperature control:

SignalSourceWiringFunction
Temperature signalTemperature sensor (PT100 / 4–20 mA)VFD AI0PID feedback, adjusts speed by temperature
Frequency referencePLC/DCS analog outputVFD AI1Remote target speed setting
Start/StopPushbutton or BA systemDI0/DI1Start/stop control
Fault outputVFD relayIntermediate relay → BA systemFault alarm
Run feedbackVFD AOBA systemOperating frequency feedback

4. Two-Speed Fan Control Panel Wiring Diagram (high/low speed switching)

Two-speed motors havetwo winding sets(e.g. 4-pole/8-pole, corresponding to 1500/750 rpm); the control panel switches the winding connection through two contactor groups:

  1. Low-speed run: KM_L contactor closes → motor low-speed winding connected in Y or delta (per nameplate) → motor runs at low speed.
  2. High-speed run: KM_H contactor closes → motor high-speed winding connected in YY (double star) → motor runs at high speed.
  3. Interlock: KM_L and KM_H normally closed auxiliary contacts interlock to prevent simultaneous pull-in and winding burnout.
  4. Switching logic: High speed to low speed → open KM_H first → delay 0.5s → close KM_L; low speed to high speed → open KM_L first → delay 0.5s → close KM_H. The delay prevents arc short circuits.
⚠️ Dual-speed motor switching precautions

When switching the motor from high speed to low speed, the rotor still rotates at close to high speed due to inertia, while the low-speed winding, once energized, has a low synchronous speed, so the motor enters aregenerative braking state, and the inrush current is large. For high-to-low switching, we recommend adding a 2-3s delay to let the motor slow down before closing the low-speed contactor, or using a VFD for soft switching.

SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — 4. Wiring diagram for a dual-speed fan control cabinetCabinet structure diagram · photo pending

5. Common mistakes in fan control cabinets (4 red lines)

🔴 Wiring non-negotiables

① Star-delta transition time too short → the fan switches to delta before reaching rated speed, causing high inrush current; ② VFD-to-fan motor cable >100m without an output reactor → high-frequency pulses break down the motor insulation; ③ high- and low-speed contactors for a dual-speed fan not interlocked → both close at once and short the winding; ④ large fans started without closing the damper first → starting load too high and the thermal overload relay trips.

FAQ FAQ

What is the difference between fan VFD and pump VFD parameters?

Mainly theV/F curve settings. Fans and pumps are both variable-torque loads, so set the V/F mode to asquare-law decreasing curve(P1300=2 or 4); at low speed the voltage drops automatically to save energy. However, fans need longer acceleration/deceleration times than pumps (larger inertia), typically 20-60s acceleration and 30-120s deceleration.

Must dual-speed fan high/low speed switching be delayed?

A delay is required. When switching from high speed to low speed, the motor is in a regenerative braking state, and closing the low-speed contactor immediately causes a large inrush current. Delay 2-3s until the motor speed drops near the low-speed synchronous speed before closing. Low-to-high switching can be done directly (motoring state, no inrush).

What star-delta starting time should be set for a fan control cabinet?

Fans have large inertia and long acceleration times. Rule of thumb: t ≈ 6 × √P (50% longer than for pumps). For a 22kW fan, t ≈ 6×√22 ≈ 28s. During actual commissioning, listen to the sound — the best switch point is when the motor changes from a humming sound to smooth running.

How much energy can a VFD fan save?

30-50%. For fans, per the affinity laws, flow ∝ speed and power ∝ speed³. Reducing speed by 10% reduces flow by 10% but reduces power by 27% (1-0.9³=0.27). Actual savings depend on damper opening and operating conditions — the smaller the original damper opening (the greater the throttling loss), the more energy is saved after a VFD retrofit.

Related pages:Technical notes · Products · Industries · Resource center · FAQ · Get a quote

Related reading

Need Distribution box, distribution cabinet? Build to drawing · MOQ 1 unit · 15–25 day delivery

A source factory in Zhejiang (Fengchuan Industrial Zone, Tonglu — 5,000 sqm, a team of 20, 5,800+ units a year), holding ISO 9001:2015 / CE(LVD+EMC) / IP65 test report. Build-to-drawing service for distribution boxes, low-voltage assemblies, PLC control cabinets and VFD panels. Free drawing review, photo/video inspection before shipment.