Package Substation Specifications
Interpreting Key Clauses of GB/T 17467

The core of package substation specifications is GB/T 17467(high-voltage/low-voltage prefabricated substations). This article interprets the key clauses: temperature rise, ingress protection, grounding, and insulation level. Zhejiang Golden Unicorn produces 300+ package substation enclosures annually and holds ISO 9001:2015 certification.

1. What Is GB/T 17467? (General Specification for Package Substations)

GB/T 17467 = High-/Low-Voltage Prefabricated SubstationA national standard specifying the structure, temperature rise, ingress protection, insulation, and grounding requirements for package substations. It is the fundamental basis for package substation design and acceptance testing in China.

SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — 1. What Is GB/T 17467Cabinet structure diagram · photo pending

2. Temperature Rise Requirements (Key Clauses)

ComponentPermissible Temperature Rise (K)
Transformer winding≤ 65
Busbar/contacts≤ 65
Enclosure≤ 30
Operating handle≤ 15

3. Ingress Protection (Enclosure Protection)

Protection

Outdoor package substation enclosure ≥ IP54(dust-proof and splash-proof), ventilation openings IP2X (finger-safe). High-voltage compartment doors must have interlocks that cut power when opened.

4. Grounding Requirements (4 Items)

  1. Grounding grid: resistance ≤ 4Ω, independent grounding
  2. Grounding busbar: copper bar ≥ 40×4mm
  3. Metal enclosure grounding: enclosure reliably connected to grounding grid
  4. PE busbar: connection between the low-voltage side PE busbar and the grounding grid

5. Insulation Level (withstand voltage)

High-voltage unit power-frequency withstand voltage: 32 kV/1 min for 6 kV systems, 42 kV/1 min for 10 kV systems. Low-voltage unit power-frequency withstand voltage: 2500 V/1 min. Every Golden Unicorn unit undergoes a power-frequency withstand voltage test before shipment, with a report included.

FAQ FAQ

Which standard must a package substation comply with?

GB/T 17467 (package substations) — the primary basis for package substation design and acceptance.

What are the temperature rise limits for a package substation?

Transformer windings ≤ 65K, enclosure ≤ 30K.

What is the ingress protection rating for an outdoor package substation?

≥ IP54, with ventilation openings rated IP2X.

What is the grounding resistance for a package substation?

≤ 4Ω, with an independent grounding grid.

Related pages:Technical notes · Products · Industries · Resource center · FAQ · Get a quote

Related reading

Need Distribution box, distribution cabinet? Build to drawing · MOQ 1 unit · 15–25 day delivery

A source factory in Zhejiang (Fengchuan Industrial Zone, Tonglu — 5,000 sqm, a team of 20, 5,800+ units a year), holding ISO 9001:2015 / CE(LVD+EMC) / IP65 test report. Build-to-drawing service for distribution boxes, low-voltage assemblies, PLC control cabinets and VFD panels. Free drawing review, photo/video inspection before shipment.