HomeTechnical notes › Distribution Box System Diagram Reading Guide: Graphical Symbols, Letter Codes and Circuit Numbering Rules

05 Informational content / Technical articles 2026-09-11 Published ~ 11 min read GB/T 6988 · GB 50054 · GB/T 7251.1

Distribution Box System Diagram Reading Guide
Graphical Symbols, Letter Codes and Circuit Numbering Rules

Reading system diagrams is a core skill for electrical engineers. This guide breaks down the three rule sets for distribution box system diagrams — graphical symbols, letter codes and circuit numbering — and includes a32-item quick-reference table of high-frequency symbols. Written for newcomers in procurement, estimating, construction and switchgear assembly plants. Zhejiang Golden Unicorn is ISO 9001 certified and produces 5000+ units per year.

1. What to Read on a System Diagram (4 Categories of Information)

InformationWhat to Look For
TopologyIncoming line → main breaker → busbar → outgoing line connections
ParameterModel, setting current, transformation ratio, current-carrying capacity
ProtectionGround fault protection parameters, SPD surge protection
MeasurementCurrent transformers, meter configuration

2. 32 High-Frequency Symbols Quick Reference (per GB/T 6988)

SymbolMeaningSymbolMeaning
QSIsolationQFCircuit breaking
KMContactFUFuse
KARelayKTTime
TACurrent transformerTVVoltage transformer
PAAmmeterPVVoltmeter
PJElectricity meterSPDSurge
WBBusbarPEGrounding
NNeutralL1/L2/L3Phase sequence
SBPushbuttonSASelector switch
HLIndicator lightHAAudible alarm
FRThermal overload relayXTTerminal
MMotor-operatedTTransformer
SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Diagram — Section 2: Quick Reference to 32 High-Frequency SymbolsCabinet structure diagram · photo pending

Section 3: Circuit Numbering Rules (How to Read L1-1-W1)

Circuit number = phase + circuit number + cable code. For example, L1-1-W1 means the first cable of circuit 1 on phase L1. On a system diagram, every outgoing feeder has a unique number that corresponds to the terminal block diagram and wiring diagram.

Section 4: 5-Step Diagram Reading Method (Hands-On)

  1. Locate theincoming feederand identify where the power comes from
  2. Locate themain breakerand check its model and settings
  3. Locate theBusbarand check its specifications and sections
  4. Count theoutgoing feedersand check the destination and protection of each circuit
  5. Check themetering and surge protectionconfiguration

Section 5: Common Diagram Reading Mistakes (3 Items)

Pitfall

① Reading only the topology and ignoring the parameters — failing to verify the setting current will cause protection failure; ② Ignoring the CT ratio — meter readings must be converted; ③ Confusing PE and N — they must be drawn separately on the system diagram.

FAQ FAQ

What is the hardest part of reading a system diagram?

Symbol. Memorize the 32 high-frequency symbols and you can read 90% of diagrams.

What is the pattern in circuit numbering?

Phase (L1/L2/L3) + circuit number (1/2/3) + cable code (W1/W2), numbered from left to right.

What if I can't draw a system diagram?

Draw it with EPLAN/CADe SIMU, or send us your requirements and Zhejiang Golden Unicorn will produce the drawing free of charge.

Does the system diagram need a stamp?

Drawings supplied with the cabinet mustbe signed by three people: designer / reviewer / approver, as required by the ISO 9001 system.

Related pages:Technical notes · Products · Industries · Resource center · FAQ · Get a quote

Related reading

Need Distribution box, distribution cabinet? Build to drawing · MOQ 1 unit · 15–25 day delivery

A source factory in Zhejiang (Fengchuan Industrial Zone, Tonglu — 5,000 sqm, a team of 20, 5,800+ units a year), holding ISO 9001:2015 / CE(LVD+EMC) / IP65 test report. Build-to-drawing service for distribution boxes, low-voltage assemblies, PLC control cabinets and VFD panels. Free drawing review, photo/video inspection before shipment.