How to Read Secondary Distribution Box Photos
Internal Layout, Circuits & Labeling Standards

The secondary distribution box is the distribution hub on a construction site, receiving power from the primary box and feeding each final-stage switch box. This article uses on-site photos to explain the internal layout, circuit arrangement and labeling standards of a secondary box, with a secondary box selection table. Zhejiang Golden Unicorn produces 5,800+ units per year,MOQ 1 unit · 15–25 days.

1. What Does a Secondary Distribution Box Look Like? (4 Structural Elements)

Typical secondary box structure: incoming disconnect switch + main ground fault protection + 3–6 outgoing circuits (each with branch isolation + branch ground fault protection) + N/PE bars. Sheet metal enclosure thickness ≥ 1.5mm, outdoor ≥ IP65.

SCHEMATICBusbarsTerminal blocksMain circuit breakerControl & protection devicesTerminal block outgoing cables
Figure — What a Secondary Distribution Box Looks LikeCabinet structure diagram · photo pending

2. Internal Layout Standards (Top to Bottom)

LocationComponent
Top — Incoming SectionIncoming cable + incoming disconnect switch
Middle — Main Switch SectionMain ground fault protection + main circuit breaker
Bottom — Outgoing SectionBranch circuit breakers (3–6 circuits)
Base — Grounding SectionN bar + PE bar + grounding terminals

3. Circuit Labeling Standards (Every Circuit Must Be Labeled)

  1. Circuit number: 1L1, 1L2, 1L3… (circuit + phase sequence)
  2. Destination label: indicates which final-stage box or equipment the circuit feeds
  3. Breaker setting value: affixed next to the switch, e.g. C32 / 40A
  4. Phase color code: L1 yellow / L2 green / L3 red / N blue / PE yellow-green

4. How to Set Branch Ground Fault Protection in a Secondary Box (100–300 mA)

Selection

RCD rated residual operating current for secondary distribution box branch circuits 100–300mA, time-delay type 0.2 s, for line protection and ground fault protection. Only the final level (tertiary box) uses ≤ 30 mA for personnel protection.Do not install 30 mA in the secondary distribution box— it will race with the final level and cause nuisance tripping.

5. Secondary Distribution Box Selection Table (by number of branch circuits)

Branch circuitsEnclosure sizeIncoming breakerBranch breaker
3 circuits500×400×20063A3× C32
4 circuits600×400×200100A4× C40
6 circuits800×600×250160A6× C63
8 circuits1000×600×250250A8× C80

FAQ FAQ

What mA rating for the RCD in a secondary distribution box?

100–300mA, time-delay type. Only the final level uses ≤ 30 mA.

Can a secondary distribution box be installed outdoors?

Yes, with ingress protection ≥ IP65, a rain hood, and at least 1.2 m above ground.

What is the difference between a secondary distribution box and a primary distribution box?

The primary box is the main distribution point (main breaker + main metering); the secondary box distributes (branch circuits to each zone); the tertiary box is the final level (connects to equipment).

Can branch circuits in a secondary distribution box feed receptacles?

Yes, but each receptacle circuit must have its own RCD rated ≤ 30 mA.

Related pages:Technical notes · Products · Industries · Resource center · FAQ · Get a quote

Related reading

Need Distribution box, distribution cabinet? Build to drawing · MOQ 1 unit · 15–25 day delivery

A source factory in Zhejiang (Fengchuan Industrial Zone, Tonglu — 5,000 sqm, a team of 20, 5,800+ units a year), holding ISO 9001:2015 / CE(LVD+EMC) / IP65 test report. Build-to-drawing service for distribution boxes, low-voltage assemblies, PLC control cabinets and VFD panels. Free drawing review, photo/video inspection before shipment.